/fs/cache/b2/b4/c9/c2/0eb305f32caeb60992ab84e8.jpg

Complete Transformer Substations of Block Type КТПБ-УЭТМ®-110

Parameters

Specifications of KTPB-UETM®:

  • Climatic version - for macroclimatic areas with temperate and cold climates (U, UHL *, UHL).
  • Category of placement - 1 (in the open air) in accordance with GOST 15150.
  • Upper operating temperature during operation plus 40 ° С.
  • Lower operating temperature during operation - minus 55 ° С (minus 60 ° С for certain types of equipment).
  • Installation height above sea level to 1000m.
  • The degree of air pollution I - IV according to GOST 9920.
  • Environment - non-explosive, not containing conductive dust and corrosive gases or gases in concentrations of destructive metals and insulation.
  • Resistance to earthquakes - up to 9 points on the MSK-64 scale.
  • The area downwind I - V, according to the PUE.
  • Ice region I - VII, according to PUE.

General parameters KTPB-UETM®:

Parameter

KTPB-UETM

LVSG

Notes

Rated voltage HVSG, kV

220

110

35

6 (10)

-

MVSG rated voltage, kV

110;35

35

-

6 (10)

-

Power transformer capacity, kVA

 До 400000

 До 125000

 До 25000

Capacity of the power transformer is selected with a specific design of substation

Rated current of open switchgear cells, A

400; 630; 1000; 1600; 2500

400; 630; 1000; 1600; 2500 

400; 630; 1000

-

-

Nominal current of the switchgear input cells, A

 630; 1000; 1600; 2500; 3150

 630; 1000; 1600; 2500; 3150

 630; 1000; 1600; 2500; 3150

 630; 1000; 1600; 2500; 3150

 -

Rated current busbars, A

 1000; 2000; 1600; 2500; 3150; 4000; 6300

 1000; 2000; 1600; 2500; 3150; 4000; 6300

630; 1000; 1600; 2500; 3150

 -

Thermal current
within 3 sec, kA

 40; 50

40; 50

12,5; 50

25; 31,5; 40

 -

Through current short
short circuit (amplitude), kA

102; 125

102; 125 

 35; 125

 63; 80; 102

 

Write us

Your message has been send succesfully!
logo

Акционерное Общество "Уралэлектротяжмаш"

Yekaterinburg,
Frontovyh brigad, 22
+7 (343) 324-52-00
secretary@uetm.ru