Complete Transformer Substations of Block Type КТПБ-УЭТМ®-110
Parameters
Specifications of KTPB-UETM®:
- Climatic version - for macroclimatic areas with temperate and cold climates (U, UHL *, UHL).
- Category of placement - 1 (in the open air) in accordance with GOST 15150.
- Upper operating temperature during operation plus 40 ° С.
- Lower operating temperature during operation - minus 55 ° С (minus 60 ° С for certain types of equipment).
- Installation height above sea level to 1000m.
- The degree of air pollution I - IV according to GOST 9920.
- Environment - non-explosive, not containing conductive dust and corrosive gases or gases in concentrations of destructive metals and insulation.
- Resistance to earthquakes - up to 9 points on the MSK-64 scale.
- The area downwind I - V, according to the PUE.
- Ice region I - VII, according to PUE.
General parameters KTPB-UETM®:
Parameter |
KTPB-UETM |
LVSG |
Notes |
||
Rated voltage HVSG, kV |
220 |
110 |
35 |
6 (10) |
- |
MVSG rated voltage, kV |
110;35 |
35 |
- |
6 (10) |
- |
Power transformer capacity, kVA |
До 400000 |
До 125000 |
До 25000 |
- |
Capacity of the power transformer is selected with a specific design of substation |
Rated current of open switchgear cells, A |
400; 630; 1000; 1600; 2500 |
400; 630; 1000; 1600; 2500 |
400; 630; 1000 |
- |
- |
Nominal current of the switchgear input cells, A |
630; 1000; 1600; 2500; 3150 |
630; 1000; 1600; 2500; 3150 |
630; 1000; 1600; 2500; 3150 |
630; 1000; 1600; 2500; 3150 |
- |
Rated current busbars, A |
1000; 2000; 1600; 2500; 3150; 4000; 6300 |
1000; 2000; 1600; 2500; 3150; 4000; 6300 |
630; 1000; 1600; 2500; 3150 |
- |
- |
Thermal current |
40; 50 |
40; 50 |
12,5; 50 |
25; 31,5; 40 |
- |
Through current short |
102; 125 |
102; 125 |
35; 125 |
63; 80; 102 |
|